Goodrive350-19 series VFD Commissioning
- 40 -
Note
: In closed-loop mode, when the encoder is abnormal, set
P90.00=1
to switch to the open-loop
vector control mode. The two modes are different in the brake timing sequence logic, and therefore
you need to adjust P01 and P90 parameters accordingly.
5.1.3 Macro parameters (P90.00=1)
Function
code
Name
Setting
Remarks
P00.00
Speed control mode
1
SVC mode 1
P00.01
Command running
channel
1
Terminal
P00.03
Max. output frequency
100.00Hz
P00.04
Upper limit of running
frequency
90.00Hz
P00.06
Setting channel of A
frequency command
15
Graded multi-step speed
P00.11
ACC time 1
8.0s
P00.12
DEC time 1
4.0s
P00.14
Carrier frequency setting
1.5kHz
P01.01
Starting frequency of direct
start
1.00Hz
P01.15
Stop speed
1.50 Hz
P01.24
Stop speed delay
0.4s
P05.00
HDI input type
0x11
HDIA is digital input
HDIB is digital input
P05.03
Function of S3 terminal
77
Graded reference terminal 1
P05.04
Function of S4 terminal
78
Graded reference terminal 2
P05.05
Function of HDIA terminal
79
Graded reference terminal 3
P05.06
Function of HDIB terminal
80
Graded reference terminal 4
P06.00
HDO output type
1
Open collector output
P06.02
HDO output selection
56
Brake detection reminding
P06.03
RO1 output selection
49
Brake output
P06.04
RO2 output selection
5
VFD fault
P11.08
VFD or motor
overload/underload alarm
0x021
Underload protection is enabled to
enhance equipment safety
P11.11
Underload pre-alarm
detection level
15%
P25.01
Function of S5 terminal
7
Fault reset
P25.02
Function of S6 terminal
75
Brake feedback signal
P90.04
Enabling brake-oriented
logic
1
The brake is controlled by the VFD.