- 167 -
Setting
Function
Description
to the master can be implemented.
72
Switch to the slave
When the terminal is valid, the switchover from the
master to the slave can be implemented.
73
Enable the VFD
When the terminal is valid, the VFD is enabled.
74
Contactor feedback signal
Contactor status feedback.
75
Brake feedback signal
Brake status feedback.
76
Operating lever zero-point
position
When the terminal is valid, the operating level sets the
zero-point input signal.
77
Graded reference terminal 1 Five terminals can be used to implement graded speed
setting.
Trml1
Trml 2
Trml 3
Trml 4
Trml 5
Speed setting
OFF
OFF
OFF
OFF
OFF
Graded setting 0
ON
OFF
OFF
OFF
OFF
Graded setting 1
ON
ON
OFF
OFF
OFF
Graded setting 2
ON
ON
ON
OFF
OFF
Graded setting 3
ON
ON
ON
ON
OFF
Graded setting 4
ON
ON
ON
ON
ON
Graded setting 5
78
Graded reference terminal 2
79
Graded reference terminal 3
80
Graded reference terminal 4
81
Graded reference terminal 5
82
Upward DEC limit position
When the terminal is valid, the VFD enters the upward
slow speed area and runs at the frequency specified by
P91.35.
83
Downward DEC limit
position
When the terminal is valid, the VFD enters the downward
slow speed area and runs at the frequency specified by
P91.35.
84
Light load speed boost
signal
When P91.08=5, the terminal command is valid, light
load speed boost is performed.
85
Brake detection
When the terminal command is valid, brake detection is
performed
86
Valid signal of PTC
overtemperature
Supporting only the terminals S5
–
S8 of EC-IO502-00.
When receiving this signal, the PTC overtemperature
alarm or fault is reported.