background image

3 G 3 J V

q u i c k   s t a r t   g u i d e

020 8450 8087

020 8450 0173

www.omron.co.uk

[email protected]

1 Apsley Way, Staples Corner, London, NW2 7HF

Fax number

020 8233 1468

Factory automation technical support

24hr technical helpsheet/datasheet faxback service

020 8450 4646

General telephone enquiries and technical support

UK website

Direct e-mail address for sales enquiries

Содержание 3G3JV Series

Страница 1: ... eu omron com 1 Apsley Way Staples Corner London NW2 7HF Fax number 020 8233 1468 Factory automation technical support 24hr technical helpsheet datasheet faxback service 020 8450 4646 General telephone enquiries and technical support UK website Direct e mail address for sales enquiries ...

Страница 2: ...ply 20mA at 12V Frequency reference input Frequency reference common Multi function contact output NC L1í L2í L3í External frequency adjuster 2 kΩ 1 4 W min Multi function input 2 S3 Multi function input 3 S4 Multi function input 4 S5 Analogue monitor output M 3G3JV PFI Standard Connections Note 1 Connect single phase 200 V AC to terminals R L1 and S L2 of the 3G3JV AB Note 2 The braking resistor ...

Страница 3: ... Set by parameter n40 during running Common for MA amd MB use Set by parameter n44 Output frequency Common for AM use Photocoupler 8 mA at 24VDC Note NPN is the default setting for these terminals No external power supply is required Refer to connections shown below 20mA at 12VDC 0 to 10VDC 20Kohms 4 to 20mA 0 to 20mA Relay output 1A max at 30VDC and 250 VAC 12mA max at 0 to 10VDC S1 S2 S3 S4 S5 S...

Страница 4: ...I3005E PFI3010E PFI3010E PFI3010E PFI3020E PFI3020E Installation Dimensions Rated Voltage Model 3G3JV Supply Recommendations Noise Filter Specifications Y W X d H L D 8 5 H1 H W1 W 5 6 Two 5 dia holes 5 H 128 128 128 128 128 128 128 128 128 128 128 128 H1 118 118 118 118 118 118 118 118 118 118 118 118 W 68 68 68 108 108 108 108 108 108 108 140 140 W1 56 56 56 96 96 96 96 96 96 96 128 128 D 70 70 ...

Страница 5: ...ugh to n79 can be set or moni tored while this indicator is lit Note While the Inverter is in operation the parameters can be only monitored and only some parameters can be changed Any RUN command input is ignored while this indicator is lit Switches the setting and monitor item indicators in sequence Parameter being set will be cancelled if this key is pressed before entering the setting Increase...

Страница 6: ...r Output 0 Output Frequency 1 Output Current Carrier Frequency Selection DC Injection Braking Current DC Injection Braking at Stop Time DC Injection Braking at Start Time Stall pevention during deceleration 0 Stall Prevention Enabled 1 Braking Resistor Enabled n01 n02 n03 n09 n10 n11 n16 n17 n21 n22 n28 n32 n36 n37 n38 n39 n40 n44 n46 n52 n53 n54 n55 0 to 9 0 1 0 to 4 20 to 400 1 to 255V 0 2 to 40...

Страница 7: ...peed reference 1 7 Multi step speed reference 2 8 Multi step speed reference 3 10 Inching command 12 External base block NO 13 External base block NC 17 Local Remote selection Multi function Outputs Value Function 0 Fault output 1 During RUN 2 Frequency agree 6 Overtorque being monitored NO 12 RUN mode 13 Inverter ready 15 Undervoltage in progress Analogue Output Functions Value Function 0 Output ...

Страница 8: ...n Comms Remote switching attempted Check your control terminal wiring A multi function digital input has been set to 12 or 13 Forward and reverse run signal have been applied simultaneously Overcurrent Output current is higher than 250 of Inverter rated current Overvoltage DC bus voltage has exceeded detection level Main circuit undervoltage DC bus voltage is below detection level Unit overheated ...

Отзывы: