Goodrive350-19 series VFD Function parameter list
- 222 -
Function
code
Name
Description
Default
value
Modify
12: Reserved
P03.15
Source of upper
limit frequency
setup of reverse
rotation in torque
control
0: Keypad (P03.17)
1: AI1 (100% corresponds to max. frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as above)
5: Multi-step (the same as above)
6: MODBUS communication (the same as above)
7: PROFIBUS /CANopen/ DeviceNet
communication (the same as above)
8: Ethernet communication (the same as above)
9: Pulse frequency HDIB (the same as above)
10: EtherCat/Profinet communication
11: PLC
12: Reserved
Note:
For the options 1-11, 100% is relative to the
max. frequency.
0
○
P03.16
Keypad limit value
of upper limit
frequency of
forward rotation in
torque control
This function code is used to set frequency limit.
100% corresponds to the max. frequency. P03.16
sets the value when P03.14=1; P03.17 sets the
value when P03.15=1.
Setting range: 0.00Hz
–P00.03 (Max. output
frequency)
50.00Hz
○
P03.17
Max. output
frequency
50.00Hz
○
P03.18
Source of upper
limit setup of the
torque during
motoring
0: Keypad (P03.20)
1: AI1 (100% relative to three times of motor
current)
2: AI2 (the same as above)
3: AI3 (the same as above)
0
○