Goodrive350-19 series VFD Function parameter list
- 333 -
Function
code
Name
Description
Default
value
Modify
P24.05
Filter times of
encoder detection
Setting range: 0x00
–0x99
Ones: Low-speed filter times, corresponds to
2^(0
–9)×125us.
Tens: High-speed filter times; corresponds to
2^(0
–9)×125us.
0x33
○
P24.06
Speed ratio
between encoder
mounting shaft
and motor
You need to set this parameter when the encoder
is not installed on the motor shaft and the drive
ratio is not 1.
Setting range: 0.001
–65.535
1.000
○
P24.07
Control
parameters of
synchronous
motor
Bit0: Enable Z pulse calibration
Bit1: Enable encoder angle calibration
Bit2: Enable SVC speed measurement
Bit3: Select resolver speed measurement mode
Bit4: Z pulse capture mode
Bit5: Do not detect encoder initial angle in v/f
control
Bit6: Enable CD signal calibration
Bit7: Disable sin/cos sub-division speed
measurement
Bit8: Do not detect encoder fault during autotuning
Bit9: Enable Z pulse detection optimization
Bit10: Enable initial Z pulse calibration
optimization
Bit12: Clear Z pulse arrival signal after stop
0x3
○
P24.08
Enable Z pulse
offline detection
0x00
–0x11
Ones: Z pulse
Reserved
Tens: UVW pulse
0: Do not detect
0x10
○