Goodrive350-19 series VFD Operating
- 195 -
In running
Fault occurred, and the
keypad displayed fault
code
Figure out the fault
cause based on the
fault code
Figure out the most possible
cause according to P07.33
–
P07.40
Run again
Proper running
Rule out
fault based on
corresponding
solutions
Consult with INVT
Y
N
N
Y
Related parameter list:
Function
code
Name
Description
Default
value
P07.27
Type of present fault
0: No fault
1: Inverter unit U phase protection (OUt1)
2: Inverter unit V phase protection (OUt2)
3: Inverter unit W phase protection
(OUt3)
4: Overcurrent during acceleration (OC1)
5: Overcurrent during deceleration (OC2)
6: Overcurrent during constant speed
(OC3)
7: Overvoltage during acceleration (OV1)
8: Overvoltage during deceleration (OV2)
0
P07.28
Type of the last fault
/
P07.29
Type of the last but one fault
/
P07.30
Type of the last but two fault
/
P07.31
Type of the last but three
fault
/
P07.32
Type of the last but four fault