Goodrive350-19 series VFD Operating
- 175 -
Setting
Function
Description
16
Simple PLC state
completed
Output signal when current stage of simple PLC is
completed
17
Simple PLC cycle
completed
Output signal when a single cycle of simple PLC
operation is completed
23
Virtual terminal output of
MODBUS communication
Output corresponding signal based on the set value of
MODBUS; output ON signal when it is set to 1, output
OFF signal when it is set to 0
24
Virtual terminal output of
Profibus/CANopen/
DeviceNet communication
Output corresponding signal based on the set value of
PROFIBUS/CANopen; output ON signal when it is set to
1, output OFF signal when it is set to 0
25
Virtual terminal output of
Ethernet communication
Output corresponding signal based on the set value of
Ethernet; output ON signal when it is set to 1, output OFF
signal when it is set to 0.
26
DC bus voltage
established
Output is valid when the bus voltage is above the
undervoltage threshold of the inverter.
27
Z pulse output
Output is valid when the encoder Z pulse is arrived, and
is invalid after 10 ms.
28
During pulse superposition Output is valid when the pulse superposition terminal
input function is valid
29
STO action
Output when STO fault occurred
30
Positioning completed
Output is valid when position control positioning is
completed
31
Spindle zeroing completed Output is valid when spindle zeroing is completed
32
Spindle scale-division
completed
Output is valid when spindle scale-division is completed
33
In speed limit
Output is valid when the frequency is limited
34
Virtual terminal output of
EtherCat/Profinet
communication
The corresponding signal is output according to the set
value of Profinet communication. When it is set to 1, the
ON signal is output, and when it is set to 0, the OFF