Goodrive350-19 series VFD Function parameter list
- 294 -
Function
code
Name
Description
Default
value
Modify
coefficient of
motor 2
P12.29
Parameter display
of motor 2
0: Display based on the motor type; under this
mode, only parameters related to current motor
type will be displayed.
1: Display all; under this mode, all the parameters
will be displayed.
0
○
P12.30
System inertia of
motor 2
0
–30.000kgm
2
0.000
○
7.2.14 P13 Control parameters of synchronous motor
Function
code
Name
Description
Default
value
Modify
P13.00
Reduction rate of
the injection
current of
synchronous
motor
This parameter is used to set the reduction rate of
the input reactive current. When the active current
of the synchronous motor increases to some
extent, the input reactive current can be reduced
to improve the power factor of the motor.
Setting range: 0.0%
–100.0% (of the rated current
of the motor)
80.0%
○
P13.01
Initial pole
detection mode
0: No detection
1: High-frequency current injection
2: Pulse superposition
0
◎
P13.02
Pull-in current 1
Pull-in current is the pole position orientation
current; pull-in current 1 is valid within the lower
limit of pull-in current switch-over frequency
threshold. If you need to increase the starting
torque, increase the value of this function code
properly.
Setting range: 0.0%
–100.0% (rated motor current)
20.0%
○