Goodrive350-19 series VFD Function parameter list
- 286 -
Function
code
Name
Description
Default
value
Modify
Setting range of P11.10: 0.01
–3600.00s
P11.11
Underload
pre-alarm
detection level
Underload pre-alarm signal will be outputted if the
output current of the VFD or motor is lower than
underload pre-alarm detection level (P11.11), and
the
duration
exceeds
underload
pre-alarm
detection time (P11.12).
Setting range of P11.11: 0
– P11.09
Setting range of P11.12: 0.01
–360.00s
25%
○
P11.12
Underload
pre-alarm
detection time
0.05s
○
P11.13
Fault output
terminal action
during fault
This function code is used to set the action of fault
output terminals during undervoltage and fault
reset.
0x00
–0x11
Ones:
0: Act during undervoltage fault
1: Do not act during undervoltage fault
Tens:
0: Act during fault reset
1: Do not act during fault reset
0x00
○
P11.14
Speed deviation
detection value
0.0
–50.0%
This parameter is used to set the speed deviation
detection value.
10.0%
○
P11.15
Speed deviation
detection time
This parameter is used to set the speed deviation
detection time. If P11.14 is set to a non-zero value,
and the speed deviation is greater than the value
of P11.14, which lasts the time specified by
P11.15, the speed deviation fault dEu is reported.
Note:
Speed deviation protection will be invalid if
P11.15 is set to 0.0.
2.0s
○