Goodrive350-19 series VFD Function parameter list
- 377 -
Function
code
Name
Description
Default
value
Modify
frequency
protection
0: Disable
1: Enable
After the function is enabled, if the brake is
opened, detection protection is performed. When
the set frequency is equal to or lower than the
value of P92.31, a fault is reported (the frequency
setting fault SFE is reported after the speed is
decreased if the speed is high); if the brake is
closed, no detection is performed.
P92.31
Set frequency
fault protection
threshold
0.00
–10.00Hz
2.00Hz
◎
P92.32
Current imbalance
multiple
0.0
–5.5
When the value is not zero, current imbalance
detection is enabled. When the 3PH current max.
value divided by the min. value is greater than this
multiple, the Cuu fault is reported.
0.0
◎
P92.33
PTC
overtemperature
protection
selection
0
–1
0: The PTC function is valid through terminal
selection, the PTC overtemperature alarm A-Ptc is
reported, but the machine still runs properly.
1: The PTC function is valid through terminal
selection, the PTC overtemperature fault PtcE is
reported, but the machine stops.
0
◎
7.2.32 P93 Hoisting closed-loop functions
Function
code
Name
Description
Default
value
Modify
P93.00
Brake slip speed
threshold
1.00
–5.00Hz
1.00Hz
○
P93.01
Brake slip fault
delay
0.000
–5.000s
The value 0 indicates brake slip is not detected,
while a non-zero value indicates brake slip is
detected. If the feedback frequency is greater than
the value of P93.00, which lasts the time specified
0.500s
○