Goodrive350-19 series VFD Operating
- 112 -
Function
code
Name
Description
Default
value
control precision is required;
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load;
3: Static autotuning 2 (partial autotuning) ;
when current motor is motor 1, only P02.06,
P02.07 and P02.08 will be autotuned; when
current motor is motor 2, only P12.06,
P12.07 and P12.08 will be autotuned.
P00.18
Function parameter
restoration
0: No operation
1: Restore to default value
2: Clear fault history
Note:
After the selected function operations
are done, this function code will be restored
to 0 automatically. Restoration to default
value will clear the user password. Exercise
caution before using this function.
0
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
P02.01
Rated power of
asynchronous motor 1
0.1
–3000.0kW
Model
depended
P02.02
Rated frequency of
asynchronous motor 1
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
P02.03
Rated speed of
asynchronous motor 1
1
–36000rpm
Model
depended
P02.04
Rated voltage of
asynchronous motor 1
0
–1200V
Model
depended
P02.05
Rated current of
asynchronous motor 1
0.8
–6000.0A
Model
depended