Goodrive350-19 series VFD Function parameter list
- 226 -
Function
code
Name
Description
Default
value
Modify
1: Reserved
Range: 0x0000
–0x1111
P03.36
Speed loop
differential gain
0.00
–10.00s
0.00s
○
P03.37
High-frequency
current loop
proportional
coefficient
Under closed-loop vector control mode (P00.00=3)
and P03.39, the current loop PI parameters are
P03.09 and P03.10; above P03.39, the PI
parameters are P03.37 and P03.38.
Setting range of P03.37: 0
–65535
Setting range of P03.38: 0
–65535
Setting range of P03.39: 0.0
–100.0% (relative to
max. frequency)
1000
○
P03.38
High-frequency
current loop
integral coefficient
1000
○
P03.39
Current loop
high-frequency
switch-over point
100.0%
○
P03.40
Inertia
compensation
enable
0: Disable
1: Enable
0
○
P03.41
Upper limit of
inertia
compensation
torque
Limit the max. inertia compensation torque to
prevent inertia compensation torque from being
too large.
Setting range: 0.0
–150.0% (rated motor torque)
10.0%
○
P03.42
Inertia
compensation
filter times
Filter times of inertia compensation torque, used to
smooth inertia compensation torque.
Setting range: 0
–10
7
○
P03.43
Inertia
identification
torque value
Due to friction force, it is required to set certain
identification torque for the inertia identification to
be performed properly.
0.0
–100.0% (rated motor torque)
10.0%
○
P03.44
Enable inertia
identification
0: No operation
1: Enable
0
◎