Goodrive350-19 series VFD Function parameter list
- 363 -
Function
code
Name
Description
Default
value
Modify
passes, the VFD increases the frequency to
P91.09. If the current detection fails, the VFD
remains the original frequency.
Note: The light-load speed-boost target frequency
setting must be higher than the set frequency.
Otherwise, speed boost cannot be implemented
although the conditions are met. If the set
frequency is higher than P91.10, the original
frequency is remained.
P91.09 setting range: 0.00
–100.00Hz
P91.10 setting range: 50.0%
–100.0%(100.0%
corresponding to the motor rated frequency)
P91.11 setting range: 0.0
–10.000s
P91.12, P91.13 setting range: 0.0
–150.0%
Note: Light load speed boost mode 1 is applicable
to the open-loop mode.
P91.14
Heavy-load
speed-limit
detection
frequency
P91.14
P91.15
Set frequency
or speed limit
frequency
Output
frequency
Time
When the set frequency is greater than the heavy
load speed-limit detection frequency (P91.14), the
motor running frequency becomes stable after
reaching the detection frequency (P91.14), and
load detection is performed after the time specified
by P91.15. The load detection value is used for
heavy load speed limit calculation. The load
detection value P94.01 can be viewed through the
keypad.
P91.14 setting range: 0.00Hz
–P02.02
P91.15 setting range: 0.00
–5.00s
P94.01 setting range: 0.0%
–150.0% (of the motor
rated torque)
40.00Hz
○
P91.15
Heavy-load
speed-limit
detection delay
0.35s
○