Goodrive350-19 series VFD Function parameter list
- 351 -
Function
code
Name
Description
Default
value
Modify
When function is enabled, the VFD will first run in
forward direction and then run in reverse direction,
so as to ensure enough torque to drive the load.
P90.06
Graded multi-step
speed reference 0
Multi-step speed setting is special for hoisting. The
five multi-step speed setting terminals can be
combined to form six speed settings
Trml1
Trml 2
Trml 3
Trml 4
Trml 5
Speed
setting
Function
code
OFF
OFF
OFF
OFF
OFF
Multi-step
setting 0
P90.06
ON
OFF
OFF
OFF
OFF
Multi-step
setting 1
P90.07
ON
ON
OFF
OFF
OFF
Multi-step
setting 2
P90.08
ON
ON
ON
OFF
OFF
Multi-step
setting 3
P90.09
ON
ON
ON
ON
OFF
Multi-step
setting 4
P90.10
ON
ON
ON
ON
ON
Multi-step
setting 5
P90.11
Set P00.06=15 or P00.07=15. The multi-step
speed setting terminals are specified by P05 or
P25, which can select functions 77
–8. The speeds
are
specified
by
P90.06
–P90.11 (P00.03
percentage of max. frequency)
P90.06, P90.07, P90.08, P90.09, P90.10, P90.11
setting range: 0.0
–
100.0%
Note:
The multi-step settings of a higher grade
can be closed only after the multi-step settings of
all lower grades are closed.
0.0%
○
P90.07
Graded multi-step
speed reference 1
0.0%
○
P90.08
Graded multi-step
speed reference 2
0.0%
○
P90.09
Graded multi-step
speed reference 3
0.0%
○
P90.10
Graded multi-step
speed reference 4
0.0%
○
P90.11
Graded multi-step
speed reference 5
0.0%
○
P90.12
Forward brake
release current
Brake timing sequence in V/F mode:
0.0%
○
Run
cmd
RVS
Output
frequency
RVS
Disable for RVS stop
Stop
Stop
Enable for RVS stop
Run
cmd
Output
frequency