Goodrive350-19 series VFD Function parameter list
- 285 -
Function
code
Name
Description
Default
value
Modify
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time t
Pre-alarm time t
Setting range of P11.08:
Enable and define overload pre-alarm function of
the VFD and motor
Setting range: 0x000
–0x131
Ones:
0: Motor overload/underload pre-alarm, relative to
rated motor current;
1: VFD overload/underload pre-alarm, relative to
rated VFD current.
Tens:
0: The VFD continues running after
overload/underload alarm;
1: The VFD continues running after underload
alarm, and stops running after overload fault;
2: The VFD continues running after overload
alarm, and stops running after underload fault;
3: The VFD stops running after overload/underload
fault.
Hundreds:
0: Always detect
1: Detect during constant-speed running
Setting range of P11.09: P11.11
–200%