Goodrive350-19 series VFD Function parameter list
- 246 -
Function
code
Name
Description
Default
value
Modify
of AI1
current corresponds to 0
–10V voltage.
In different applications, 100% of analog setting
corresponds to different nominal values.
The figure below illustrates several settings.
-100%
100%
Corresponding setting
AI
-10V
10V
20mA
0
AI2
AI1
Input filter time: Adjust the sensitivity of analog
input, increase this value properly can enhance
the anti-interference capacity of analog variables;
however, it will also degrade the sensitivity of
analog input.
Note:
AI1 can support 0
–10V/0–20mA input, when
AI1 selects 0
–20mA input; the corresponding
voltage of 20mA is 10V; AI2 supports -10V
–+10V
input.
Setting range of P05.24: 0.00V
–P05.26
Setting range of P05.25: -300.0%
–300.0%
Setting range of P05.26: P05.24
–10.00V
Setting range of P05.27: -300.0%
–300.0%
Setting range of P05.28: 0.000s
–10.000s
Setting range of P05.29: -10.00V
–P05.31
Setting range of P05.30: -300.0%
–300.0%
Setting range of P05.31: P05.29
–P05.33
Setting range of P05.32: -300.0%
–300.0%
Setting range of P05.33: P05.31
–P05.35
Setting range of P05.34: -300.0%
–300.0%
P05.27
Corresponding
setting of upper
limit of AI1
100.0%
○
P05.28
Input filter time of
AI1
0.030s
○
P05.29
Lower limit value
of AI2
-10.00V
○
P05.30
Corresponding
setting of lower
limit of AI2
-100.0%
○
P05.31
Intermediate
value 1 of AI2
0.00V
○
P05.32
Corresponding
setting of
intermediate
value 1 of AI2
0.0%
○
P05.33
Intermediate
value 2 of AI2
0.00V
○
P05.34
Corresponding
setting of
intermediate
value 2 of AI2
0.0%
○
P05.35
Upper limit value
of AI2
10.00V
○
P05.36
Corresponding
setting of upper
limit of AI2
100.0%
○
P05.37
Input filter time of
AI2
0.030s
○