Goodrive350-19 series VFD Operating
- 120 -
Function
code
Name
Description
Default
value
0: Reserved
1: Reserved
Tens place: Reserved
0: Reserved
1: Reserved
Hundreds place: ASR integral separation
enabling
0: Disabled
1: Enabled
Thousands place: Reserved
0: Reserved
1: Reserved
Range: 0x0000
–0x1111
P03.36
ASR differential gain
0.00
–10.00s
0.00s
P03.37
High-frequency ACR
proportional coefficient
In the closed-loop vector control mode
(P00.00=3), when the frequency is lower
than the ACR high-frequency switching
threshold (P03.39), the ACR PI parameters
are P03.09 and P03.10; and when the
frequency is higher than the ACR
high-frequency
switching
threshold
(P03.39), the ACR PI parameters are
P03.37 and P03.38.
Setting range of P03.37: 0
–20000
Setting range of P03.38: 0
–20000
Setting range of P03.39: 0.0
–100.0%
(relative to the maximum frequency)
1000
P03.38
High-frequency ACR
integral coefficient
1000
P03.39
ACR high-frequency
switching threshold
100.0%
P17.32
Flux linkage
0.0
–200.0%
0.0%
6.5.4 SVPWM control mode
GD350-19 VFD also carries built-in SVPWM control function. SVPWM mode can be used in cases
where mediocre control precision is enough. In cases where a VFD needs to drive multiple motors, it