Goodrive350-19 series VFD Function parameter list
- 375 -
Function
code
Name
Description
Default
value
Modify
P92.18
Digital of PT100
calibration lower
limit
calibration first:
Step 1. Select two temperature points as the
calibration temperature upper and lower limits.
Step 2. Test the sampling values of the resistance
values corresponding to the two calibration
temperature points and use the sampling values
as the calibration temperature upper and lower
limit digitals (after calibration temperature points
are set, digitals can be directly transferred after the
enabling is performed by setting P92.26).
PT1000 temperature calibration uses the same
rule.
P92.15 setting range: 50.0
–150.0°C
P92.16 setting range: -20.0
–50.0°C
P92.17, P92.18 setting range: 0
–4096
Note:
If the temperature measurement range is
from -20°C to 150.0°C, it is recommended that
10°C and 120°C be used as the
calibration
temperature points.
1270
○
P92.19
PT1000
overtemperature
protection point
0.0
–150.0°C
120.0°C
○
P92.20
PT1000
overtemperature
alarm point
0.0
–150.0°C
100.0°C
○
P92.21
PT1000
calibration
temperature
upper limit
Temperature
sampling value
Temperature
P92.21
P92.22
P92.23
P92.24
P92.21 setting range: 50.0
–150.0°C
P92.22 setting range: -20.0
–50.0°C
P92.23, P92.24 setting range: 0
–4096
120.0°C
○
P92.22
PT1000
calibration
temperature lower
limit
10.0°C
○
P92.23
Digital of PT1000
calibration upper
limit
3100
○
P92.24
Digital of PT1000
calibration lower
1100
○