Goodrive350-19 series VFD Function parameter list
- 233 -
Function
code
Name
Description
Default
value
Modify
Setting range: 0.0
–3600.0s
P04.31
Output max.
voltage
Set the upper/lower limit value of output voltage.
Vmax
Vmin
V set
Time t
t1
t2
t1=P04.29
t2=P04.30
Setting range of P04.31: P04.32
–100.0% (rated
motor voltage)
Setting range of P04.32: 0.0%
–P04.31
100.0%
◎
P04.32
Output min.
voltage
0.0%
◎
P04.33
Flux-weakening
coefficient in the
constant power
zone
1.00
–1.30
1.00
○
P04.34
Input current 1 in
synchronous
motor VF control
When the synchronous motor VF control mode is
enabled, this parameter is used to set the reactive
current of the motor when the output frequency is
lower than the frequency set in P04.36.
Setting range: -100.0%
–+100.0% (of the rated
current of the motor)
20.0%
○
P04.35
Input current 2 in
synchronous
motor VF control
When the synchronous motor VF control mode is
enabled, this parameter is used to set the reactive
current of the motor when the output frequency is
higher than the frequency set in P04.36.
Setting range: -100.0%
–+100.0% (of the rated
current of the motor)
10.0%
○
P04.36
Frequency
threshold for input
current switching
in synchronous
motor VF control
When the synchronous motor VF control mode is
enabled, this parameter is used to set the
frequency threshold for the switching between
input current 1 and input current 2.
Setting range: 0.00 Hz
–P00.03 (Max. output
50.00Hz
○