Function
code
Name
Description
Default
value
P03.11
Torque setup mode
selection
1: Set via keypad (P03.12)
2: Set via AI1 (100% corresponds to three
times of rated motor current)
3: Set via AI2 (the same as above)
4: Set via AI3 (the same as above)
5: Set via pulse frequency HDIA (the same
as above)
6: Set via multi-step torque (the same as
above)
7: Set via MODBUS communication (the
same as above)
8: Set via PROFIBUS/CANopen/DeviceNet
communication (the same as above)
9: Set via Ethernet communication (the
same as above)
10: Set via pulse frequency HDIB (the
same as above)
11: Set via EtherCat/Profinet
communication
12: Set via PLC
Note:
For the options 2
–12, 100%
corresponds to three times of rated motor
current.
1
P03.12
Torque set by keypad
-300.0%
–300.0% (motor rated current)
50.0%
P03.13
Torque reference filter time 0.000
–10.000s
0.010s
P03.14
Source of upper limit
frequency setup of forward
rotation in torque control
0: Keypad (P03.16)
1: AI1 (100% corresponds to max.
frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
0