Goodrive350-19 series VFD Operating
- 146 -
Function
code
Name
Description
Default
value
mode valid in SVPWM mode)
1: Detection value of speed
P01.18
Power-on terminal running
protection selection
0: Terminal running command is invalid
at power up
1: Terminal running command is valid at
power up
0
P01.19
Action selection when the
running frequency is below
lower limit (lower limit should
be larger than 0)
0: Run at the lower limit frequency
1: Stop
2: Sleep
0
P01.20
Wake-up-from-sleep delay
0.0
–3600.0s (valid when P01.19 is 2)
0.0s
P01.21
Restart after power cut
0: Restart is disabled
1: Restart is enabled
0
P01.22
Waiting time of restart after
power cut
0.0
–3600.0s (valid when P01.21 is 1)
1.0s
P01.23
Start delay
0.0
–60.0s
0.0s
P01.24
Stop speed delay
0.0
–100.0s
0.0s
P01.25
Open-loop 0Hz output
selection
0: No voltage output
1: With voltage output
2: Output as per DC brake current of stop
0
P01.26
Deceleration time of
emergency-stop
0.0
–60.0s
2.0s
P01.27
Time of starting section of
deceleration S curve
0.0
–50.0s
0.1s
P01.28
Time of ending section of
deceleration S curve
0.0
–50.0s
0.1s
P01.29
Short-circuit brake current
0.0
–150.0% (rated VFD current)
0.0%