Goodrive350-19 series VFD Function parameter list
- 358 -
Function
code
Name
Description
Default
value
Modify
frequency point horizontal moving), torque control is applied when
the frequency is lower than P90.45, while speed
control is applied when the frequency is higher
than P90.45.
7.2.30 P91 Extended functions for hoisting
Function
code
Name
Description
Default
value
Modify
P91.00
Enabling conical
motor functions
The conical motor does not require external
braking since it implements braking by using
internal magnetic flux control. During start, the
starting frequency needs to be increased for brake
release. During stop, quick demagnetizing needs
to be implemented to prevent slip in case of
overdue brake closing.
P91.00 setting range: 0
–1
0: Disable
1: Enable
P91.01 setting range: P91.02
–150.0%
(100% corresponding to the motor rated voltage)
P91.02 setting range: P91.03
–P91.01
P91.03 setting range: 0.0
–P91.02
0
◎
P91.01
Conical motor
ACC process
voltage coefficient
K1
120.0%
○
P91.02
Conical motor
constant process
voltage coefficient
K2
100.0%
○
P91.03
Conical motor
DEC process
voltage coefficient
K3
80.0%
○