Goodrive350-19 series VFD Operating
- 174 -
Setting
Function
Description
running
2
In forward running
Output ON signal when there is frequency output during
forward running
3
In reverse running
Output ON signal when there is frequency output during
reverse running
4
In jogging
Output ON signal when there is frequency output during
jogging
5
VFD fault
Output ON signal when VFD fault occurred
6
Frequency level detection
FDT1
Refer to P08.32 and P08.33
7
Frequency level detection
FDT2
Refer to P08.34 and P08.35
8
Frequency reached
Refer to P08.36
9
Running in zero speed
Output ON signal when the VFD output frequency and
reference frequency are both zero.
10
Reach upper limit
frequency
Output ON signal when the running frequency reaches
upper limit frequency
11
Reach lower limit
frequency
Output ON signal when the running frequency reached
lower limit frequency
12
Ready to run
Main circuit and control circuit powers are established,
the protection functions do not act; when the VFD is
ready to run, output ON signal.
13
In pre-exciting
Output ON signal during pre-exciting of the VFD
14
Overload pre-alarm
Output ON signal after the pre-alarm time elapsed based
on the pre-alarm threshold; see P11.08
–P11.10 for
details.
15
Underload pre-alarm
Output ON signal after the pre-alarm time elapsed based
on the pre-alarm threshold; see P11.11
–P11.12 for
details.