Goodrive350-19 series VFD Operating
- 136 -
Function
code
Name
Description
Default
value
11: Reserved
Note:
Source 1
–10, 100% relative to three times
of motor current.
P03.19
Source of upper
limit setup of brake
torque
0: Keypad (P03.21)
1: AI1 (100% relative to three times of motor
current)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as above)
5: MODBUS communication (the same as
above)
6: PROFIBUS/CANopen/DeviceNet
communication (the same as above)
7: Ethernet communication (the same as above)
8: Pulse frequency HDIB (the same as above)
9: EtherCat/Profinet communication
10: PLC
11: Reserved
Note:
Source 1
–10, 100% relative to three times
of motor current.
0
P03.20
Set upper limit of
the torque when
motoring via
keypad
0.0
–300.0% (rated motor current)
180.0%
P03.21
Set upper limit of
brake torque via
keypad
0.0
–300.0% (rated motor current)
180.0%
P17.09
Motor output
torque
-250.0
–250.0%
0.0%
P17.15
Torque reference
value
-300.0
–300.0% (rated motor current)
0.0%