Goodrive350-19 series VFD Function parameter list
- 218 -
Function
code
Name
Description
Default
value
Modify
protection
coefficient of
motor 1
In is rated motor current, lout is VFD output
current, K is motor overload protection coefficient.
The smaller the K, the larger the value of M, and
the easier the protection.
M=116%: protection will be applied when motor
overloads for 1h; M=200%: protection will be
applied when motor overloads for 60s; M>=400%:
protection will be applied immediately.
1m
1h
116%
200 %
Time t
Motor overload multiple
Setting range: 20.0%
–120.0%
P02.28
Power display
calibration
coefficient of
motor 1
This function adjusts the power display value of
motor 1 only, and it does not affect the control
performance of the VFD.
Setting range: 0.00
–3.00
1.00
○
P02.29
Parameter display
of motor 1
0: Display as per motor type; under this mode, only
parameters related to current motor type will be
displayed.
1: Display all; under this mode, all the motor
parameters will be displayed.
0
○
P02.30
System inertia of
motor 1
0
–30.000kgm2
0
○
P02.31
–
P02.32
Reserved
variables
0
–65535
0
○