Goodrive350-19 series VFD Optional peripheral accessories
-510-
VFD model
Recommended
cable size
(mm
2
)
Connectable cable size (mm
2
)
Terminal
screw
specs.
Tightening
torque
(Nm)
RST
UVW
PE
RST
UVW
P1
(+)
PB
(+), (-)
PE
GD350-19-110G-4-B
120
70
70~120 70~120 70~120 50~70
M12
35
GD350-19-132G-4
185
95
95~300 95~300 95~300 95~240
Terminals use nuts,
and therefore you are
recommended to use a
wrench or sleeve.
GD350-19-160G-4
240
120
95~300 95~300 95~300 120~240
GD350-19-185G-4
95*2P
95
95~150 70~150 70~150 35~95
GD350-19-200G-4
95*2P
120
95*2P
~150*2P
95*2P
~150*2P
95*2P
~150*2P
120~240
GD350-19-220G-4 150*2P 150
95*2P
~150*2P
95*2P
~150*2P
95*2P
~150*2P
150~240
GD350-19-250G-4
95*4P 95*2P
95*4P
~150*4P
95*4P
~150*4P
95*4P
~150*4P
95*2P
~150*2P
GD350-19-280G-4
95*4P 95*2P
95*4P
~150*4P
95*4P
~150*4P
95*4P
~150*4P
95*2P
~150*2P
GD350-19-315G-4
95*4P 95*4P
95*4P
~150*4P
95*4P
~150*4P
95*4P
~150*4P
95*2P
~150*2P
GD350-19-355G-4
95*4P 95*4P
95*4P
~150*4P
95*4P
~150*4P
95*4P
~150*4P
95*2P
~150*2P
GD350-19-400G-4 150*4P 150*2P
95*4P
~150*4P
95*4P
~150*4P
95*4P
~150*4P
95*2P
~150*2P
GD350-19-450G-4 150*4P 150*2P
95*4P
~150*4P
95*4P
~150*4P
95*4P
~150*4P
95*2P
~150*2P
GD350-19-500G-4 150*4P 150*2P
95*4P
~150*4P
95*4P
~150*4P
95*4P
~150*4P
95*2P
~150*2P
Note:
Cables of the sizes recommended for the main circuit can be used in scenarios where the
ambient temperature is lower than 40°C, the wiring distance is shorter than 100 m, and the
current is the rated current.
The terminals P1, (+), PB, and (-) are used to connect to DC reactors and braking accessories.