Goodrive350-19 series VFD Function parameter list
- 343 -
Function
code
Name
Description
Default
value
Modify
0: Follow the master to start
1: Determined by P00.01
Hundreds: Slave transmitting/master receiving
data enable
0: Enable
1: Disable
P28.03 Slave speed gain 0.0
–
500.0%
100.0%
○
P28.04 Slave torque gain 0.0
–
500.0%
100.0%
○
P28.05
Speed/torque
mode switching
frequency point of
master/slave
mode 2
0.00
–
10.00Hz
5.00Hz
○
P28.06 Number of slaves 0
–
15
1
◎
P28.07
Master/slave
transmission unit
pulse ratio
0.00
–100.00
1.00
○
P28.08
Position
synchronization
deviation
deadzone setting
0
–50000
When the position difference is greater than
P28.08, correction on the slave is valid.
50
○
P28.09
Position
synchronization
deviation
threshold
0
–
50000
When the position difference is greater than
P28.09, the master/slave position fault (ELS) is
reported.
1000
○
P28.10
Position
synchronization
regulator output
limit
0.0
–
100.0%
5.0%
○
P28.11
Position
synchronization
pulse count reset
method
0
–1
0: Automatic
During stop, the position synchronization pulse
count is automatically reset.
1: Terminal based
If the input terminal selects the position
synchronization pulse count reset function, the
0
◎