Goodrive350-19 series VFD Quick startup
- 6 -
Whether there is direct sunlight or biological invasion in the environment where the VFD is
to be used. If yes, take more protective measures.
Whether there is dust or inflammable and explosive gas in the environment where the VFD
is to be used. If yes, take more protective measures.
2.5 Checking after installation
Check the following after the VFD installation is complete.
Whether the input power cables and motor cables meet the current-carrying capacity
requirements of the actual load.
Whether the peripheral accessories are correctly selected and properly installed, and
whether the installation cables meet the current-carrying capacity requirements of these
accessories, including the input reactor, input filter, output reactor, output filter, DC reactor,
braking unit, and braking resistor.
Whether the VFD is installed on flame-retardant materials, and whether its accessories
(such as the reactors and braking resistor) that generate heat are kept away from
flammable materials.
Whether all the control cables and power cables are separately wired and whether EMC
specification requirements are taken into full account during the wiring.
Whether all the grounding systems are properly grounded.
Whether all VFD installation clearances of the meet the requirements stated in the manual.
The installation mode of the VFD complies with the requirements in the manual. Vertical
installation is recommended whenever possible.
Whether the external wiring terminals are tightened, and whether the torque meets the
requirements.
Take protective measures to ensure that no screws, cables, or other conductive objects
drop into the VFD.
2.6 Basic commissioning
Do as follows to complete basic commissioning before the use:
1. Select the motor type, set motor parameters and select VFD control modes according to
actual motor parameters.
2. Check whether autotuning is needed. If possible, disconnect the motor load to perform
dynamic parameter autotuning. If the load cannot be disconnected, perform static
autotuning.
3. Adjust the acceleration and deceleration time based on actual load working conditions.
4. Perform jogging to carry out device commissioning. Check whether the motor rotational
direction is consistent with the required direction. If no, you are advised to change the
motor rotational direction by exchanging the motor wiring of any two phases.
5. Set all the control parameters, and carry out actual running.