Goodrive350-19 series VFD Function parameter list
- 241 -
Function
code
Name
Description
Default
value
Modify
83: Downward DEC limit position
84: Light load speed boost signal
85: Brake detection
86:
Valid signal
of PTC overtemperature
(Supporting only the terminals S5
–
S8 of
EC-IO502-00)
87: Position synchronization pulse counting reset
88: Switchover between motors 1 and 3
89: Anti-snag protection input
P05.08
Polarity of input
terminal
This function code is used to set the polarity of
input terminals.
When the bit is set to 0, input terminal polarity is
positive;
When the bit is set to 1, input terminal polarity is
negative;
0x000
–0x3F
0x000
○
P05.09
Digital filter time
Set S1
–S4, filter time of HDI terminal sampling. In
cases where interference is strong, increase the
value of this parameter to avoid mal-operation.
0.000
–1.000s
0.010s
○
P05.10
Virtual terminal
setting
0x000
–0x3F (0: disable, 1: enable)
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: HDIA virtual terminal
BIT5: HDIB virtual terminal
0x00
◎
P05.11
2/3 Wire control
mode
Used to set the 2/3 Wire control mode.
0: 2-Wire control 1; integrate enabling function with
direction. This mode is the most popular dual-line
mode. Direction of motor rotation is determined by
the defined FWD/REV terminal command.
0
◎