Goodrive350-19 series VFD Operating
- 154 -
Function
code
Name
Description
Default
value
P05.26
Upper limit value of AI1
P05.24
–10.00V
10.00V
P05.27
Corresponding setting of
upper limit of AI1
-100.0%
–100.0%
100.0%
P05.28
Input filter time of AI1
0.000s
–10.000s
0.100s
P05.29
Lower limit value of AI2
-10.00V
–P05.31
-10.00V
P05.30
Corresponding setting of
lower limit of AI2
-100.0%
–100.0%
-100.0%
P05.31
Intermediate value 1 of AI2
P05.29
–P05.33
0.00V
P05.32
Corresponding setting of
intermediate value 1 of AI2
-100.0%
–100.0%
0.0%
P05.33
Intermediate value 2 of AI2
P05.31
–P05.35
0.00V
P05.34
Corresponding setting of
intermediate value 2 of AI2
-100.0%
–100.0%
0.0%
P05.35
Upper limit value of AI2
P05.33
–10.00V
10.00V
P05.36
Corresponding setting of
upper limit of AI2
-100.0%
–100.0%
100.0%
P05.37
Input filter time of AI2
0.000s
–10.000s
0.100s
P05.38
HDIA high-speed pulse input
function
0: Set input via frequency
1: Reserved
2: Input via encoder, used in
combination with HDIB
0
P05.39
Lower limit frequency of
HDIA
0.000 KHz
– P05.41
0.000KHz
P05.40
Corresponding setting of
lower limit frequency of HDIA
-100.0%
–100.0%
0.0%
P05.41
Upper limit frequency of
P05.39
–50.000KHz
50.000KHz