Goodrive350-19 series VFD Function parameter list
- 234 -
Function
code
Name
Description
Default
value
Modify
frequency)
P04.37
Reactive current
closed-loop
proportional
coefficient in
synchronous
motor VF
When the synchronous motor VF control mode is
enabled, this parameter is used to set the
proportional coefficient of the reactive current
closed-loop control.
Setting range: 0
–3000
50
○
P04.38
Reactive current
closed-loop
integral time in
synchronous
motor VF control
When the synchronous motor VF control mode is
enabled, this parameter is used to set the integral
coefficient of the reactive current closed-loop
control.
Setting range: 0
–3000
30
○
P04.39
Reactive current
closed-loop
output limit in
synchronous
motor VF control
When the synchronous motor VF control mode is
enabled, this parameter is used to set the output
limit of the reactive current in the closed-loop
control. A greater value indicates a higher reactive
closed-loop compensation voltage and higher
output power of the motor. In general, you do not
need to modify this parameter.
Setting range: 0
–16000
8000
○
P04.40
Enable I/F mode
for asynchronous
motor 1
0: Disabled
1: Enabled
0
◎
P04.41
Current setting in
I/F mode for
asynchronous
motor 1
When I/F control is adopted for asynchronous
motor 1, this parameter is used to set the output
current. The value is a percentage in relative to the
rated current of the motor.
Setting range: 0.0
–200.0%
120.0%
○
P04.42
Proportional
coefficient in I/F
mode for
asynchronous
When I/F control is adopted for asynchronous
motor 1, this parameter is used to set the
proportional coefficient of the output current
closed-loop control.
350
○