Goodrive350-19 series VFD Operating
- 158 -
Setting
Function
Description
(bipolar)
26
Running speed (bipolar)
0
–Max. output frequency
27
EtherCat/Profinet
communication set value 2
-1000
–1000, 1000 corresponds to 100.0%
28
C_AO1 from PLC
1000 corresponds to 100.0%
29
C_AO2 from PLC
1000 corresponds to 100.0%
30
Running speed
0
–Two times of rated synchronous speed of motor
31
–47
Reserved variable
Related parameter list:
Function
code
Name
Description
Default
value
P06.00
HDO output type
0: Open collector high-speed pulse
output
1: Open collector output
0
P06.14
AO1 output selection
0: Running frequency
1: Set frequency
2: Ramps reference frequency
3: Running speed
4: Output current (relative to twice the
VFD rated current)
5: Output current (relative to twice the
motor rated current)
6: Output voltage (relative to 1.5 times
the VFD rated voltage)
7: Output power (relative to twice the
motor rated power)
8: Set torque value (relative to twice the
motor rated torque)
9: Output torque (relative to twice the
0
P06.15
Reserved variable
0
P06.16
HDO high-speed pulse output
0