Goodrive350-19 series VFD Function parameter list
- 282 -
Function
code
Name
Description
Default
value
Modify
unit
seconds;
1: min; the running time of each step is counted in
minutes;
7.2.12 P11 Protection parameters
Function
code
Name
Description
Default
value
Modify
P11.00
Phase-loss
protection
0x000
–0x1111
Ones place: Reserved
Tens place:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds place:
0: Disable hardware input phase loss protection
1: Enable hardware input phase loss protection
Thousands place:
0: During stop, if a hardware input phase loss fault
occurs, it reports SPI.
1: During stop, if a hardware input phase loss fault
occurs, it reports A-SPI.
Model
depended
○
P11.01
Frequency-drop at
transient power
down
0: Disable
1: Enable
0
○
P11.02
Energy braking
selection for stop
0: Enable
1: Disable
0
◎
P11.03
Overvoltage stall
protection
0: Disable
1: Enable
0
○