Goodrive350-19 series VFD Function parameter list
- 381 -
Function
code
Name
Description
Default
value
Modify
1:1
1:2
1:4
Note:
The suspension ratio is related to the pulley
through which the steel rope goes.
P93.11
Rope length
compensation
Rope length to compensate the distance from the
center of gravity of the weight to the hook.
0.00m
–50.00m
0.00m
○
P93.12
Cable diameter (1) To measure heights correctly in closed-loop
mode, the actual running distance of the motor is
calculated by using the encoder pulse count.
Before first running, the upward limit position must
be calibrated.
Do as follows:
Set the upward limit position terminal, for example,
P05.05=64. Then the HDI terminal functions as the
upward limit position input.
If internal measurement (motor encoder) is
enabled, set P93.08=1.
Start the tower crane to run upward and stop at the
upward limit position.
Record the values of P93.14 and P93.15.
(2) In open/closed loop mode, if external
measurement (HDI) is enabled, set P93.08=2.
Start the tower crane to run upward and stop at the
upward limit position.
P93.12 setting range: 0.1
–100.0mm
P93.13 setting range: 1
–200
P93.14 setting range: 0
–P93.13 (Winding turns of
10.0
○
P93.13
Per-layer turns of
drum winding
30
○
P93.14
Initial turns of
drum winding
0
○
P93.15
Initial diameter of
drum/pulley
diameter
600.0
◎