Goodrive350-19 series VFD Commissioning
- 84 -
Function
code
Name
Description
Default
setting
P28.09
Position
synchronization
deviation threshold
0
–50000
When the position difference is greater than
P28.09, a master/slave position fault is
reported.
1000
P28.10
Position
synchronization
regulator output limit
0.0
–100.0%
5.0%
P28.11
Position
synchronization pulse
count reset method
0
–1
0: Automatic
During stop, the position synchronization pulse
count is automatically reset.
1: Terminal based
If the input terminal selects the position
synchronization pulse count reset function, the
pulse count is automatically reset when there is
signal input.
0
P28.12
Position
synchronization
proportional coefficient
0.000
–10.000
0.005
P28.13
Position
synchronization
integral time
0.01
–80.00s
8.00s
P28.14
Position
synchronization filtering
time
0.00
–10.00s
0.05s
5.11 Motor and macro switchover
5.11.1 Switchover description
The VFD provides three sets of motor parameters, and you can switch between motors through the
terminal switching function. First, you need to set the ones place of P08.31 to 0, and then use input
terminal function 35 (switching motor 1 to motor 2) and input terminal function 88 (switching to motor
3) to perform motor switchover.
In addition, application macros can be switched. Set P90.03 to set the terminal-based method of
switching application macros, and set P90.00 and P90.01 to select application macros. After the
corresponding motor is switched, the application macro is switched accordingly.
The wiring diagram for motor switching is as follows (you can see the example in section 5.11.2 for
the VFD reference terminals):