Goodrive350-19 series VFD Function parameter list
- 214 -
Function
code
Name
Description
Default
value
Modify
P01.30
Hold time of
short-circuit brake
at startup
enter short-circuit brake.
During stop, if the running frequency of VFD is
below the starting frequency of brake after stop,
set P01.31 to a non-zero value to enter
short-circuit brake after stop, and then carry out
DC brake in the time set by P01.12 (refer to
P01.09
–P01.12).
Setting range of P01.29: 0.0
–150.0% (VFD)
Setting range of P01.30: 0.0
–50.0s
Setting range of P01.31: 0.0
–50.0s
0.00s
○
P01.31
Hold time of
short-circuit brake
at stop
0.00s
○
P01.32
Pre-exciting time
for jogging
0
–10.000s
0.000s
○
P01.33
Starting frequency
of stop braking
during jogging
0
–P00.03
0.00Hz
○
P01.34
Delay to enter the
sleep state
0
–3600.0s
0.0s
○
7.2.3 P02 Parameters of motor 1
Function
code
Name
Description
Default
value
Modify
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
◎
P02.01
Rated power of
asynchronous
motor 1
0.1
–3000.0kW
Model
depended
◎
P02.02
Rated frequency
of asynchronous
motor 1
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
◎
P02.03
Rated speed of 1
–36000rpm
Model
◎