Goodrive350-19 series VFD Function parameter list
- 271 -
Function
code
Name
Description
Default
value
Modify
0: Save during power down
1: Zero out during power down
Hundreds: Action selection for frequency setup (by
DP communication) during power down
0: Save during power down
1: Zero out during power down
P08.48
High bit of initial
value of power
consumption
Set the initial value of power consumption.
Initial value of power consumption=P08.48×1000+
P08.49
Setting range of P08.48: 0
–59999 kWh (k)
Setting range of P08.49: 0.0
–999.9 kWh
0°
○
P08.49
Low bit of initial
value of power
consumption
0.0°
○
P08.50
Flux braking
This function code is used to enable flux braking
function.
0: Invalid
100
–150: The larger the coefficient, the stronger
the brake intensity
The VFD enables motor to decelerate quickly by
increasing the motor flux which converts energy
generated during braking into thermal energy.
The VFD monitors motor state continuously even
during flux braking, thus flux braking can be
applied in motor stop or used to change motor
speed. The flux braking also carries the following
advantages.
1)
Brake
immediately
after
sending
stop
command, removing the need to wait for flux to
attenuate.
2) Better cooling effect. During flux braking, the
stator current of the motor increases, while the
rotor current does not change, while the cooling
effect of stator is much more effective than that of
0
○