Goodrive350-19 series VFD Function parameter list
- 357 -
Function
code
Name
Description
Default
value
Modify
Running
command
Output
frequency
FWD
RVS
Though the brake closing command has been
output during stop, the VFD accepts a new start
command.
P90.39 setting range: 0.0
–10.0s
P90.40
Braking method in
open-loop vector
control
0
–4
0: Common mode
1: Torque limit mode
2: Torque/speed switchover mode 1 (boost with
braking)
3: DC braking mode
4: Torque/speed switchover mode 2 (horizontal
moving)
0
◎
P90.41
Torque limit 1 in
open-loop vector
control
Setting range: 0.0
–300.0% (of the motor rated
current)
(P90.40=1 torque limit mode)
120.0%
○
P90.42
Torque setting for
brake release
0.0
–
200.0%
The brake is released when the feedback value
is >= 80% of the set value if P90.40=2
(Torque/speed switchover mode 1).
120.0%
○
P90.43
Brake open delay
after startup DC
braking starts
0.00
–50.00s
If P90.40=3 (DC braking mode), after the startup
DC braking starts, the brake opens with a delay.
The delay must be equal to or less than the startup
DC braking time.
0.00s
○
P90.44
Brake closing
delay after stop
DC braking starts
0.00
–50.00s
If P90.40=3 (DC braking mode), after the stop DC
braking starts, the brake closes with a delay. The
delay must be equal to or less than the stop DC
braking time.
0.00s
○
P90.45
Torque/speed
switchover
0.00
–50.00Hz
If P90.40=4 (Torque/speed switchover mode 2,
8.00Hz
◎