Goodrive350-19 series VFD Operating
- 156 -
adjusted by setting the max. value, min. value, and the percentage of their corresponding output.
Analog output signal can output motor speed, output frequency, output current, motor torque and
motor power at a certain proportion.
0
1
2
3
.
.
.
.
.
.
19
20
P06.14
P06.16
AO1
HDO
P06.17
P06.18
P06.19
P06.20
P06.27
P06.28
P06.29
P06.30
P06.21
P06.31
(Default value is 0)
(Default value is 0)
P06.00
(HDO output type)
0
1
P06.00
0: Open collector high-speed
pulse output
1: Open-collector output
Analog output curve setting
Analog output selection
Analog output filter
Instructions for output:
Setting
Function
Description
0
Running frequency
0
–Max. output frequency
1
Set frequency
0
–Max. output frequency
2
Ramps reference frequency
0
–Max. output frequency
3
Running speed
0
–Synchronous speed corresponding to Max. output
frequency
4
Output current (relative to
VFD)
0
–Two times of rated current of VFD
5
Output current (relative to
motor)
0
–Two times of rated current of motor
6
Output voltage
0
–1.5 times of rated voltage of VFD
7
Output power
0
–Two times of rated power
8
Set torque value
0
–Two times of rated current of motor
9
Output torque
0
–Two times of rated current of motor