Goodrive350-19 series VFD Function parameter list
- 209 -
Function
code
Name
Description
Default
value
Modify
Output frequency f
Time t
fmax
t1
t2
Note:
When it is set to 1, set P01.06, P01.07,
P01.27 and P01.28 accordingly.
P01.06
Time of starting
section of
acceleration S
curve
The curvature of S curve is determined by
acceleration range and acceleration and
deceleration time.
Output frequency f
Time t
t1
t2
t3
t4
t1=P01.06
t2=P01.07
t3=P01.27
t4=P01.28
Setting range: 0.0
–50.0s
0.1s
◎
P01.07
Time of ending
section of
acceleration S
curve
0.1s
◎
P01.08
Stop mode
0: Decelerate to stop; after stop command is valid,
the VFD lowers output frequency based on the
deceleration mode and the defined deceleration
time, after the frequency drops to the stop speed
(P01.15), the VFD stops.
1: Coast to stop; after stop command is valid, the
VFD stops output immediately, and the load coasts
to stop as per mechanical inertia.
0
○
P01.09
Starting frequency
of DC brake after
stop
Starting frequency of DC brake after stop; during
decelerating to stop, when this frequency is
reached, DC brake will be performed after stop.
Demagnetization time (waiting time of DC brake
after stop): Before the DC brake, the VFD will
block output, and after the demagnetization time
0.00Hz
○
P01.10
Waiting time of
DC brake after
stop
0.00s
○