Goodrive350-19 series VFD Operating
- 181 -
Function
code
Name
Description
Default
value
P07.40
Output terminal state of
present fault
0
P17.13
Digital output terminal
state
0
6.5.13 Simple PLC
Simple PLC is a multi-step speed generator, and the VFD can change the running frequency and
direction automatically based on the running time to fulfill process requirements. Previously, such
function was realized with external PLC, while now, the VFD itself can achieve this function.
GD350-19 series VFD can realize 16-step speeds control, and provide four groups of
acceleration/deceleration time for you to choose from.
After the set PLC completes one cycle (or one section), one ON signal can be output by the
multi-function relay.
Setup of running
parameters of each
PLC stage
Restart running
after the first
section
Continue running at
the frequency when
interruption occurred
Stop after running
once
Keep running in the
final value after
running once
Cyclic running
0
1
2
P10.00
(
simple PLC mode
)
PLC mode
0
1
0
1
0
1
Normal running
P10.01 (simple PLC memory selection)
No memory
after power off
Memory after
power off
P10.36
(PLC restart mode)
P17.00
Power cut during
running
Terminal function 23
Simple PLC stop reset
Set frequency
Digital output 16
Simple PLC state completed
Digital output 17
Simple PLC cycle completed
Related parameter list:
Function
code
Name
Description
Default
value
P05.01
–
P05.06
Digital input function
selection
23: Simple PLC stop reset
24: Simple PLC pausing
25: PID control pausing
P06.01
–
P06.04
Digital output function
selection
16: Simple PLC phase reached
17: Simple PLC cycle reached