Goodrive350-19 series VFD Function parameter list
- 315 -
Function
code
Name
Description
Default
value
Modify
encoder detection Ones: Low-speed filter time, corresponds to
2^(0
–9)×125us.
Tens: High-speed filter times, corresponds
to2^(0
–9)×125us.
P20.06
Speed ratio
between encoder
mounting shaft
and motor
You need to set this parameter when the encoder
is not installed on the motor shaft and the drive
ratio is not 1.
Setting range: 0.001
–65.535
1.000
○
P20.07
Control
parameters of
synchronous
motor
Bit0: Enable Z pulse calibration
Bit1: Enable encoder angle calibration
Bit2: Enable SVC speed measurement
Bit3: Select resolver speed measurement mode
Bit4: Z pulse capture mode
Bit5: Do not detect encoder initial angle in v/f
control
Bit6: Enable CD signal calibration
Bit7: Disable sin/cos sub-division speed
measurement
Bit8: Do not detect encoder fault during autotuning
Bit9: Enable Z pulse detection optimization
Bit10: Enable initial Z pulse calibration
optimization
Bit12: Clear Z pulse arrival signal after stop
0x0003
○
P20.08
Enable Z pulse
offline detection
0x00
–0x11
Ones: Z pulse
0: Do not detect
1: Enable
Tens: UVW pulse (for synchronous motor)
0: Do not detect
0x10
○