Goodrive350-19 series VFD Operating
- 155 -
Function
code
Name
Description
Default
value
HDIA
P05.42
Corresponding setting of
upper limit frequency of
HDIA
-100.0%
–100.0%
100.0%
P05.43
HDIA frequency input filter
time
0.000s
–10.000s
0.030s
P05.44
HDIB high-speed pulse input
function selection
0: Set input via frequency
1: Reserved
2: Input via encoder, used in
combination with HDIA
0
P05.45
Lower limit frequency of
HDIB
0.000 KHz
– P05.47
0.000KHz
P05.46
Corresponding setting of
lower limit frequency of HDIB
-100.0%
–100.0%
0.0%
P05.47
Upper limit frequency of
HDIB
P05.45
–50.000KHz
50.000KHz
P05.48
Corresponding setting of
upper limit frequency of
HDIB
-100.0%
–100.0%
100.0%
P05.49
HDIB frequency input filter
time
0.000s
–10.000s
0.030s
P05.50
AI1 input signal type
0
–1
0: Voltage type
1: Current type
0
Note:
When you set P90.04=1
and use the analog reference frequency, use terminals to give the
forward and reverse running commands.
6.5.10 Analog output
GD350-19 series VFD carries one analog output terminal (0
–10V/0–20mA) and one high-speed pulse
output terminal. Analog output signals can be filtered separately, and the proportional relation can be