Goodrive350-19 series VFD Function parameter list
- 288 -
Function
code
Name
Description
Default
value
Modify
P11.19
Proportional
coefficient of
current regulator
during
undervoltage stall
This parameter is used to set the proportional
coefficient of the active current regulator during
undervoltage stall.
Setting range: 0
–1000
25
○
P11.20
Integral coefficient
of current
regulator during
undervoltage stall
This parameter is used to set the integral
coefficient of the active current regulator during
undervoltage stall.
Setting range: 0
–2000
150
○
P11.21
Proportional
coefficient of
voltage regulator
during
overvoltage stall
This parameter is used to set the proportional
coefficient of the bus voltage regulator during
overvoltage stall.
Setting range: 0
–1000
60
○
P11.22
Integral coefficient
of voltage
regulator during
overvoltage stall
This parameter is used to set the integral
coefficient of the bus voltage regulator during
overvoltage stall.
Setting range: 0
–1000
10
○
P11.23
Proportional
coefficient of
current regulator
during
overvoltage stall
This parameter is used to set the proportional
coefficient of the active current regulator during
overvoltage stall.
Setting range: 0
–1000
60
○
P11.24
Integral coefficient
of current
regulator during
overvoltage stall
This parameter is used to set the integral
coefficient of the active current regulator during
overvoltage stall.
Setting range: 0
–2000
250
○
P11.25
Enable VFD
overload integral
0: Disabled
1: Enabled
When this parameter is set to 0, the overload
timing value is reset to zero after the VFD is
stopped. In this case, the determination of VFD
0