Goodrive350-19 series VFD Function parameter list
- 385 -
Function
code
Name
Description
Default
value
Modify
2
P93.26
Time t
Output
frequency
P93.28
P93.26
Loose rope
protection
Output
torque
VFD
status
Normal
SLE
fault
1: Mode 2. The VFD outputs the loose rope
protection alarm (A-SL), changes the direction,
and runs upward at the frequency specified by
P93.31, and the VFD runs downward only when
the time specified by P93.30 is reached or the
loose rope status disappears.
P93.26
Time t
Output
frequency
P93.28
P93.26
Loose rope
protection
Output
torque
VFD
status
Normal
A-SL alarm
P93.31
Target
frequency
P93.30
P93.30 setting range: 0
–20.00s
P93.31 setting range: 1.00Hz
–10.00Hz