Goodrive350-19 series VFD Function parameter list
- 213 -
Function
code
Name
Description
Default
value
Modify
Output frequency
Running
Power off
Power on
Running
t
t1
t2
t1=P01.22
t2=P01.23
Setting range: 0.0
–3600.0s (valid when P01.21 is
1)
P01.23
Start delay
This function code sets the delay of the VFD
’s
wake-up-from-sleep after running command is
given, the VFD will start to run and output after the
time set by P01.23 elapses to realize brake
release.
Setting range: 0.0
–600.0s
0.0s
○
P01.24 Stop speed delay 0.0
–600.0s
0.0s
○
P01.25
Open-loop 0Hz
output selection
0: No voltage output
1: With voltage output
2: Output as per DC brake current of stop
0
○
P01.26
Deceleration time
of
emergency-stop
0.0
–60.0s
2.0s
○
P01.27
Time of starting
section of
deceleration S
curve
0.0
–50.0s
0.1s
◎
P01.28
Time of ending
section of
deceleration S
curve
0.0
–50.0s
0.1s
◎
P01.29
Short-circuit brake
current
When the VFD starts in direct start mode
(P01.00=0), set P01.30 to a non-zero value to
0.0%
○