Goodrive350-19 series VFD Commissioning
- 83 -
Function
code
Name
Description
Default
(master/slave mode 0) first and then switches to
the torque mode at a certain frequency point
(master/slave mode 1).
3: Master/slave mode 3 (Reserved)
(Both the master and slave adopt speed
control, and the slave performs power balance
depending on the speed loop integral result of
the master.)
4: Master/slave mode 4 (Closed-loop
master/slave mode)
The master and slave must be equipped with
encoders. The master and slave adopt speed
control, using position pulse difference for
speed correction.
Tens: Slave start command source selection
0: Follow the master to start
1: Determined by P00.01
Hundreds: indicates whether to enable slave
transmitting/master receiving
0: Enable
1: Disable
P28.03
Slave speed gain
0.0
–500.0%
100.0%
P28.04
Slave torque gain
0.0
–500.0%
100.0%
P28.05
Speed/torque mode
switching frequency
point of master/slave
mode 2
0.00
–10.00Hz
5.00
P28.06
Number of slaves
0
–15
1
P28.07
Master/slave
transmission unit pulse
ratio for position
synchronization
0.00
–100.00
1.00
P28.08
Position
synchronization
deviation deadzone
0
–50000
When the position difference is greater than
P28.08, correction on the slave is valid.
50