Goodrive350-19 series VFD Function parameter list
- 257 -
Function
code
Name
Description
Default
value
Modify
P07.07
Displayed
parameter
selection for
stopped state
0x0000
–0xFFFF
0x00FF
P07.08
Frequency display
coefficient
0.01
–10.00
Display frequency=running frequency× P07.08
1.00
○
P07.09
Speed display
coefficient
0.1
–999.9%
Mechanical speed=120×display running
frequency×P07.09/number of motor pole pairs
100.0%
○
P07.10
Linear speed
display coefficient
0.1
–999.9%
Linear speed=mechanical speed×P07.10
1.0%
○
P07.11
Temperature of
rectifier bridge
module
-20.0
–120.0°C
/
●
P07.12
Temperature of
VFD module
-20.0
–120.0°C
/
●
P07.13
Software version
of control board
1.00
–655.35
/
●
P07.14
Accumulated
running time
0
–65535h
/
●
P07.15
High bit of VFD
power
consumption
Display the power consumption of the VFD.
VFD power consumption=P07.15×1000+P07.16
Setting range of P07.15: 0
–65535 kWh (×1000)
Setting range of P07.16: 0.0
–999.9 kWh
/
●
P07.16
Low bit of VFD
power
consumption
/
●
P07.17 Reserved
/
/
P07.18
Rated power of
VFD
0.4
–3000.0kW
/
●