Goodrive350-19 series VFD Function parameter list
- 360 -
Function
code
Name
Description
Default
value
Modify
1: Controlled by the VFD
P91.05
Contactor
feedback
detection time
0.00
–20.000s
1.000s
◎
P91.06
Enabling
operating lever
zero point position
detection
0x00
–0x11
Ones place
0: Disable zero point position detection
1: Enable zero point position detection
Tens place:
0: Not detect AI2
1: Detect AI2
0
◎
P91.07
Operating lever
zero point position
delay
After the zero position detection signal is enabled,
the terminal zero position signal is given in stop
state, the zero position detection is completed
(valid) with a delay specified by P91.07, the zero
position signal is released, and the VFD runs only
after being given with the running command. After
the zero position signal detection takes effect, if
both the zero position signal and running
command signal are detected, the operating lever
zero position fault STC is reported. If the running
command is given during zero position detection,
the VFD does not respond. If both the zero
position signal and running command signal still
exist after zero position detection, the operating
lever zero position fault STC is also reported. If the
zero position signal is removed suddenly during
zero position detection, the VFD does not respond
to the running command since zero position
detection is incomplete.
0.300s
○