Estimated Time:   20-30 Minutes          
Level:  1 
Prerequisite: 

• 

S15 Application Note 1.1.0 

       Navigating Menus & Parameters

      

S15 Application Note 1.8.0 

Startup Guide 

Setup and program the basic parameters. 

Visual Inspection 

□ 

No foreign materials (metal shavings, hardware)

 

 

Input and Output Wiring

   

□ 

Input leads are not wired to output terminals   

□ 

Input, output and control wires are in separate conduit   

□ 

Motor leads do not share conduit with any other motor leads   

□ 

Verify input and output wire tightness and condition (continuity, frayed wires, loose connections, 
pinched insulation)   

 

Motor Terminal Box

   

□ 

Verify no power factor correction capacitors are installed 

□ 

Verify wire tightness and condition (continuity, frayed wires, loose connections, pinched insulation)

 

 

Drive to Motor Ground Connection

 (ASD chassis to motor chassis)   

□ 

Verify wire tightness and condition (continuity, frayed wires, loose connections, pinched insulation) 

 

Record the Electrical Distribution System 

Grounding Capacitor   

  Enabled   

  Disabled

 

This should be 

DISABLED

 on Ungrounded, Corner Grounded or High Impedance Grounding Systems 

otherwise it could result in a VFD failure. Refer to Section 1.3.3 of the S15 Instruction Manual E6582175 
for more details. 

STEP

  

A

 

Startup Checklist 

 

Delta/Wye with Grounded Secondary

Содержание S15

Страница 1: ... and output wire tightness and condition continuity frayed wires loose connections pinched insulation Motor Terminal Box Verify no power factor correction capacitors are installed Verify wire tightness and condition continuity frayed wires loose connections pinched insulation Drive to Motor Ground Connection ASD chassis to motor chassis Verify wire tightness and condition continuity frayed wires l...

Страница 2: ... the keypad Sink Source Motor Rotation Run the drive at 5 Hz with the keypad default setting If incorrect swap two of the output leads T1 T2 or T3 and retest rotation Verify motor rotates in the correct direction Blower Cooling Fan s Check Verify fans operate and air flows in correct direction bottom to top Analog Inputs Verify polarity Scaling can be adjusted with parameters F201 to F221 VIC 4 20...

Страница 3: ...ult Forward Run Function Parameters f111 f151 f155 Assigned Function Terminal R Default Reverse Run Function Parameters f112 f152 f156 Assigned Function Terminal RES Default Reset Function Parameters f113 f153 N A Assigned Function Terminal S1 Default Preset Speed 1 Function Parameters f114 f154 N A Assigned Function Function Parameters f115 f116 f117 Assigned Function Terminal S2 Default Preset S...

Страница 4: ... Refer to Section 11 7 of the S15 Instruction Manual E6582175 for more details Analog Outputs Refer to S15 App Note 1 4 0 Analog Output Calibration for calibration procedure and parameters Verify analog output operation Terminal Function Parameter Default FM fmsl Output Frequency New Function Assigned Function Parameters f132 N A Assigned Function Terminals FLA FLB FLC Default Fault Status Functio...

Страница 5: ...ency Reference 0 Setting dial 1 acc Acceleration Time 1 10 0 s dec Deceleration Time 1 10 0 s fh Maximum Frequency 80 0 Hz ul Upper Limit Frequency 60 0 Hz ll Lower Limit Frequency 0 0 Hz vl Base Frequency 1 Motor Nameplate Frequency 60 0 Hz vlv Base Frequency Voltage 1 Motor Nameplate Voltage 230 460 or 575V pt V Hz Control Mode Selection 0 Constant Torque f701 Current Voltage Display Unit Select...

Страница 6: ...hiba com 855 803 7089 13131 West Little York Road Houston TX Model Information Record the model information from the nameplate sticker and CPU versions through monitor mode STEP C Model Information Information Details Type Serial No Infromation Details CPU1 Version CPU2 Version ...

Отзывы: